system is reduced by the presence of a steel reinforcement beneath the 
road surface. Ideally allow for a distance of 150 mm between loop cable 
and steel reinforcement.

In order to obtain an optimal working of the system it is advisable to 
use the RIB loops.
Figures 2A and 2B represent examples of connection of these loops 
to the detector.

W

ORKING INSTRUCTIONS

RESET/CALIBRATION PUSH-BUTTON

The  RESET  push-button  makes  it  possible  to  initialize  the  detector  and 
automatically  acquire  the  parameters  of  the  loop  connected  for  correct 
functioning.

N.B.   

Making  sure  that  there  is  no  metallic  mass  on  the  loop,  press  the 

RESET  push-button  to  carry  out  an  automatic  calibration  of  the 
detector. 

The RESET push-button must be pressed each time the position of one 
more dip-switches is varied.

LED (FIG 4) 

 

At power-on and during the calibration phase, the LED remains steady 
for approximately 3 sec and flashes for 3 more sec. 

 

The led turns on when the presence of a metallic body is detected.

SETTING AT WORK

 

Realize the connections for the undecal socket as shown in Fig. 4 and 
subsequently insert the detector as shown in the same figure. 

 

Set  up  the  frequency  through  the  dip-switches  1  and  2  as  shown  in 
Fig. 3. The change of  frequency is mainly useful to avoid interference 
between two near loops (2-3 m); in this last case it is necessary to set 
up different frequencies. As a general rule the frequency must be low for 
large loop and high for small loop. 

In most cases, it is recommended 

that the frequency is set on the MEDIUM LOW value (DIP 1-2 = ON-
OFF).

 

Set up the sensitivity through the dip-switches 3 and 4 as shown in Fig. 
3.  Setting  the  sensitivity  allow  to  forbid  the  detection  of  metallic  body 
with little dimensions such as bicycle and motorcycle. 

-   Output OUT1 may be set for impulsive (100 ms) functioning or presence 

functioning through the dip-switch 8 (Fig. 3).

 

Output  OUT2  may  be  set  for  impulsive  (100  ms)  functioning  with 
activation on the entrance or on the exit of the loop; otherwise this output 
may be set to presence functioning, through the dip-switches 6 and 7 
(Fig. 3). 

 

Be sure that there is no metallic mass on the loop, and press the RESET 
push-button to carry out an automatic calibration of the detector. 

 

Carry  out  sensitivity  tests  with  the  various  types  of  vehicles  that  the 
device must detect. If necessary, vary the setting of dip-switches 3 and 
4 until the desired sensitivity level is obtained. It is not advisable to use 
excessively high sensitivity values. 

 

 In most cases, it is recommended that the sensitivity is set on the 
MEDIUM LOW value (DIP 3-4 = ON-OFF)

 

 

Once  the  optimal  sensitivity  level  has  been  established,  if  necessary 
enable the BOOST function using dip-switch 5.   

 

Presence time set up 

   The dip switch SW10 (see Fig. 5) allows the setting of the presence time 

between 5 min and ‘infinite’, once the “presence” mode of output OUT2 
and OUT1 has been set.

 

 

If 5 min is selected, the relay is energised on detecting the earth and 
remains energised for 5 minutes if the earth remains on the loop, after 
which the relay de-energises. When the earth abandons the loop, the 
device  automatically  calibrates  without  the  operator  having  to  operate 
externally.

 

 

If ‘infinite’ is selected, the relay is energised on detecting the earth and 
remains energised for the entire time in which the earth remains above 
the loop.

 

 

To  access  the  dip-switch,  remove  the  electronic  card  from  the  plastic 
box.

 

 

Once the dip-switch is set, the electronic card must be re-inserted in the 
plastic box by following the indications given in Fig. 6, taking care that 
the card is positioned between the second and the third guide.

3

Содержание ACG9060

Страница 1: ...PIRA MAGNETICA DETECTEUR SPIRE MAGN TIQUE METALLIC MASS DETECTOR MAGNETIKWINDUNGSSENSOR SENSOR A ESPIRA MAGNETICA cod ACG9063 ACG9060 ITALIANO pag 02 FRAN AIS pag 05 ENGLISH page 08 DEUTSCH pag 11 ESP...

Страница 2: ...All interno degli angoli del circuito occorre praticare un taglio trasversale inclinato a 45 Ci consente di ridurre il rischio che il cavo della spira venga danneggiato in prossimit dei vertici degli...

Страница 3: ...ia di impostare la frequenza sul valore MEDIO BASSO DIP 1 2 ON OFF Impostare la sensibilit tramite i dip switch 3 e 4 come indicato in Fig 3 La regolazione della sensibilit permette di interdire la ri...

Страница 4: ...C B A 1 24 V 230 VAC 2 GND 230 VAC 3 N O OUT 1 N O OUT 1 4 COM OUT 1 COM OUT 1 5 N O OUT 2 N O OUT 2 6 COM OUT 2 COM OUT 2 7 LOOP LOOP 8 LOOP LOOP 9 12 V N U 10 N C OUT 2 N C OUT 2 11 N C OUT 1 N C O...

Страница 5: ...s du circuit il est n cessaire de pratiquer une coupe transversale inclin e 45 Ceci permet de r duire le risque d endommager le c ble de la spire proximit des sommets des angles droits Largeur nominal...

Страница 6: ...a valeur MOYENNE BASSE DIP 1 2 ON OFF S lectionner la sensibilit l aide des commutateurs DIP 3 et 4 comme l indique la Fig 3 Le r glage de la sensibilit permet d interdire la d tection de corps m tall...

Страница 7: ...C B A 1 24 V 230 VAC 2 GND 230 VAC 3 N O OUT 1 N O OUT 1 4 COM OUT 1 COM OUT 1 5 N O OUT 2 N O OUT 2 6 COM OUT 2 COM OUT 2 7 LOOP LOOP 8 LOOP LOOP 9 12 V N U 10 N C OUT 2 N C OUT 2 11 N C OUT 1 N C O...

Страница 8: ...detector connection cable must also be laid in an appropriate groove running from one of the circuit angles along the circuit perimeter to the road surface edge To ensure wiring continuity between the...

Страница 9: ...little dimensions such as bicycle and motorcycle Output OUT1 may be set for impulsive 100 ms functioning or presence functioning through the dip switch 8 Fig 3 Output OUT2 may be set for impulsive 10...

Страница 10: ...5 4 C B A 1 24 V 230 VAC 2 GND 230 VAC 3 N O OUT 1 N O OUT 1 4 COM OUT 1 COM OUT 1 5 N O OUT 2 N O OUT 2 6 COM OUT 2 COM OUT 2 7 LOOP LOOP 8 LOOP LOOP 9 12 V N U 10 N C OUT 2 N C OUT 2 11 N C OUT 1 N...

Страница 11: ...ndem geeignete F hrungskan le unter Verwendung von Schneidewerkzeugen f r Mauerwerk oder hnlichem hergestellt werde Innerhalb der Ecken des Kreises ist die Ausf hrung eines Querschnitts mit 45 Neigung...

Страница 12: ...n F llen empfehlt sich die Einstellung der Frequenz auf den MITTLEREN BIS NIEDRIGEN Wert DIP 1 2 ON OFF Stellen Sie die Empfindlichkeit mit Hilfe der Dip Switches 3 und 4 wie in Abb 3 gezeigt ein Die...

Страница 13: ...13 C B A 1 24 V 230 VAC 2 GND 230 VAC 3 N O OUT 1 N O OUT 1 4 COM OUT 1 COM OUT 1 5 N O OUT 2 N O OUT 2 6 COM OUT 2 COM OUT 2 7 LOOP LOOP 8 LOOP LOOP 9 12 V N U 10 N C OUT 2 N C OUT 2 11 N C OUT 1 N C...

Страница 14: ...estructuras parecidas En el interior de los ngulos del circuito es preciso efectuar un corte transversal inclinado a 45 Este corte permite reducir el riesgo que el cable de la espira resulte da ado do...

Страница 15: ...a frecuencia en el valor MEDIO BAJO DIP 1 2 ON OFF Programar la sensibilidad mediante los conmutadores DIP 3 y 4 como se indica en la Fig 3 La regulaci n de la sensibilidad permite impedir la detecci...

Страница 16: ...5 4 C B A 1 24 V 230 VAC 2 GND 230 VAC 3 N O OUT 1 N O OUT 1 4 COM OUT 1 COM OUT 1 5 N O OUT 2 N O OUT 2 6 COM OUT 2 COM OUT 2 7 LOOP LOOP 8 LOOP LOOP 9 12 V N U 10 N C OUT 2 N C OUT 2 11 N C OUT 1 N...

Страница 17: ...17 17 NOTES...

Страница 18: ...18 18 NOTES...

Страница 19: ...le champ d application de l art 6 paragraphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant que l installation ait t d clar e confor...

Страница 20: ...ry systems SENSORE A SPIRA MAGNETICA Cod CVA1321 01072008 Rev 01 Questo prodotto stato completamente progettato e costruito in Italia Ce produit a t compl tement d velopp et fabriqu en Italie This pro...

Отзывы: