MAN-000020-00 REV A
20
Getting Started
The LCD display on
REVOLUTION
™
series presents various screens and
SCREEN
MESSAGES
.
1. Powering the Charger
Energize the AC mains at the main panel (turn the local AC disconnect switch
to the
ON
position, if one exists).
Verify that the LCD display is lit and displays the
CONNECT BATTERY
screens, alternating between the animation and message as shown below.
DANGEROUS VOLTAGES AND CURRENTS ARE PRESENT IN THE AC
MAINS WHEN ENERGIZED. ONLY TRAINED PERSONNEL SHOULD
PERFORM THESE CHECKS, USING PROPER EQUIPMENT AND
PROCEDURES.
If the charger does not power up, carefully verify the source circuit and wiring
to the charger and correct any problems. If appropriate, check that all fuses in
the local disconnect switch box on the wall are intact, and that the supply
voltage for all three phases (AC mains line-to-line) is 480V ± 10%, and
matches to within 10VAC or better between phases.
Restart the charger; if the problem persists, contact the Dealer or Power
Designers USA LLC.
WARNING