MAN-000020-00 REV A
16
Figure 10: RV05 terminal block location
7. Verify the line and ground connections of the outlet or junction box/disconnect.
8. Energize the source circuit and verify proper AC voltage to the Charger. All line-
to-line voltages should be 480 VAC ± 10% and matched within 10 VAC. De-
energize the source circuit.
9. Verify that the source circuit is locked and tagged out. Once electrical installation
is complete, the cover and (2) 8-32 screws fastening the cover can be replaced.
THE CHARGER IS NOW READY FOR OPERATION