15
Figure 9: KO location
4. Pass the 480 VAC input power wires through, using the appropriate conduit or
strain relief fittings per local and national codes.
5. Crimp a #10 ring tongue terminal to the ground (
GND
) wire and connect it to the
GND terminal (Figure 9).
Tighten the nut to 15 in-lb +- 2 in-lb
.
6. Strip the conductors back 0.5 inch (12 mm) and connect them to the terminal
block (Figure 10, labelled L3 L2 L1).
Tighten the terminal screws to 12 in-lb +-
2 in-lb.
NOTE:
The charger is not phase-rotation sensitive. Be sure any excess
wire is kept away from the fans and output connections.