Probe resistance
Indoor unit probe, evaporator; indoor unit probe, ambient air
Temperature
[°C]
Resistance [k
W
]
0
35.20
5
26.88
10
20.72
15
16.12
20
12.64
25
10.00
30
7.97
35
6.40
12.2 Indoor unit fault analysis
Error code:
E0 / F4
Reason:
The control board of the outdoor unit or indoor unit cannot read the unit memory
(EEPROM)
Cause:
n
Installation error
n
Control boards of outdoor unit or indoor unit defective
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
YES
Replace the circuit boards of the outdoor unit
and indoor unit in turn, in order to locate the
defective EEPROM
51