Wind
If the unit is being installed in windy areas, ensure
that the warm outlet air is discharged in the pre-
vailing wind direction. If this is not the possible, it
may be necessary to install a windbreak (to be pro-
vided by the customer). Ensure that the windbreak
does not adversely affect the air intake to the unit.
1
Fig. 28: Windbreak
1: Wind
Snow
The unit should be wall-mounted in areas of heavy
snowfall. Installation should be at least 20cm
above the expected level of snow to prevent snow
from entering the outdoor unit. An optional wall
bracket is available as an accessory.
20 cm
1
Fig. 29: Minimum clearance to snow
1: Snow
Installation inside buildings
n
Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts,
adjoining rooms or halls (Fig. 30).
n
Install an additional fan with a rated flow com-
parative to that of the outdoor unit being
installed in the room and which can compen-
sate any additional pressure loss in ventilation
n
Comply with any regulations and conditions
affecting the statics of the building. If neces-
sary, fit acoustic installation.
2
1
K
3
W
3
Fig. 30: Installation inside buildings
K: Cold fresh air
W: Warm air
1: Outdoor unit
2: Additional fan
3: Air shaft
5.3 Installation materials
The indoor unit is attached to the wall by a wall
bracket and 4 screws (to be provided by the cus-
tomer).
The outdoor unit is attached by 4 screws and a
wall bracket to the wall or fixed by a floor bracket to
the ground.
REMKO RXT...DC
26
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......