Malfunction indicated by flashing code RXT 523-1403 DC
Error description
Number
of flashes
per
second)
LED timer
Error
code
EEPROM error, indoor unit
1
OFF
E0
Communication error between indoor unit and outdoor unit
2
OFF
E1
Evaporator fan motor speed control not OK
4
OFF
E3
Room air temperature probe faulty
5
OFF
E4
Evaporator temperature probe faulty
6
OFF
E5
No cooling capacity after 30 minutes
7
OFF
EC
Condensate pump liquid level switch triggered
8
OFF
EE
Safety shut-down due to increased power consumption
1
ON
F0
Outdoor unit air inlet temperature probe faulty
2
ON
F1
Condenser outlet temperature probe faulty
3
ON
F2
Temperature probe for heat gas line faulty
4
ON
F3
EEPROM error, outdoor unit
5
ON
F4
Condenser fan speed control not OK
6
ON
F5
Suction pipe temperature probe in AT faulty
7
ON
F6
Inverter error
1
FLASHES
P0
Over/undervoltage error
2
FLASHES
P1
Safety shut-down compressor excess temperature
3
FLASHES
P2
Safety shut-down due to low outside temperature
4
FLASHES
P3
Compressor control faulty
5
FLASHES
P4
Mode conflict
6
FLASHES
P5
Low pressure alarm
7
FLASHES
P6
REMKO RXT...DC
50
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......