Error code:
F0
Reason:
Safety shutdown due to overly high current consumption of individual unit components
Cause:
n
Faulty power supply
n
Cooling circuit blocked
n
Faulty control board
n
Electrical connections faulty
n
Compressor defective
Check the supply voltage. Is this correct?
NO
Switch the unit off and ensure correct supply
voltage.
YES
Check the cooling circuit for any blockages. Is
the cooling circuit OK?
NO
Remove the blockage (shut-off valve open?)
YES
Check the winding resistances of the com-
pressor. Are they OK?
NO
Replace the compressor.
YES
Check the electrical connections. Are these cor-
rectly implemented?
NO
Replace or correct the electrical connections.
YES
Does the transformer operate fault-free?
NO
Replace the transformer or control boards of
the outdoor unit.
YES
Replace the outdoor unit.
57
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......