Malfunction
Possible causes
Checks
Remedial measures
The unit is running but
only provides reduced or
no cooling or heating
capacity
Filter is dirty / air inlet /
outlet opening is blocked
by debris
Have the filters been
cleaned?
Clean the filters
Windows and doors
open. Heating / cooling
load has increased
Have structural / usage
modifications been
made?
Close windows and
doors / install additional
units
Neither cooling nor
heating mode has been
set
Does the cooling symbol
appear on the display?
Correct the settings for
the unit
Fins on outdoor unit
blocked by foreign
objects
Is the fan on the outdoor
component running? Are
the fins unobstructed?
Check the fan or winter
fan speed control,
reduce the air resistance
Leaking cooling cycle
Are there signs of frost
on the exchanger fins of
the indoor unit?
Repair by specialist
Outdoor unit iced up
Check outdoor unit. Has
the cassette probe on
the outdoor unit been
correctly positioned?
De-ice and fit the probe
at the point where the
most ice forms
Condensate discharge
on unit
Drainage pipe on collec-
tion container clogged /
damaged
Can the condensate
drain off without any
obstruction?
Clean the drainage pipe
and collection container
Faulty external conden-
sate pump or float
Is the collection tray full
of water and the pump
not running?
Call out a specialist to
replace the pump
Condensate has not
drained away and has
collected in the conden-
sate drainage line
Is there an incline on the
condensate drainage
line? Check there is no
blockage in the pipe.
Route the condensate
drainage line with an
incline and clean
Condensate does not
drain off
Are the condensate
drainage lines unblocked
and is there a steady
incline? Are the conden-
sate pump and liquid
level switch functioning
correctly?
Route the condensate
drainage line with an
incline and clean it. If the
liquid level switch or the
condensate pump is
defective, have them
replaced
Float is stuck or jammed
due to excessive dirt
Are the LEDs on the
receiver unit of the
indoor unit flashing?
Should be cleaned by
specialist firm
NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not
a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it
and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter
then you can switch off the breaker. Switch it back on again at least 12 hours before the next time that
the unit will be required!
49
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......