Troubleshooting 

 
This unit has been designed based on state-of-the-art manufacturing methods and it has been tested repeatedly to 
ensure that it is working properly. However, should problems occur, refer to the following list. 
Please keep in mind that the indoor units are supplied with power via the outdoor parts. As a result, we recommend 
also reading the section "Troubleshooting" in the operating instructions for the indoor unit. 

Should the unit still not be working despite these checks, please contact an authorised service centre. 

Problem 

Possible cause 

Check 

Remedy 

The unit does not start or 
it switches itself off 
automatically. 

Power failure, power too low,  

Are all other electrical components 
working? 

Check current and wait for the de-
vice to start again 

Power fuse / power supply defective 

Are all currents for lighting func-
tional? 

Replace power fuse / 
Switch on main switch 

Power supply line damaged 

Are all other electrical components 
working? 

Maintenance by authorised per-
sonnel 

Amount of time waited after switching 
unit on was too short 

Did approx. 5 minutes elapse after 
restarting? 

Plan for longer waiting periods 

Operating temperature too low / too 
high 

Are the fans on the indoor unit and 
outdoor part working? 

Pay attention to temperature 
ranges of indoor unit and outdoor 
part 

Excess current caused by thunder-
storms 

Was there recently lightning in the 
region ? 

Switch the system off and then 
back on again / Maintenance by 
authorised personnel 

Problem with the external condensa-
tion pump 

Did the pump switch off due to a 
malfunction? 

Check pump and clean if neces-
sary 

Sensors that are defective or not prop-
erly attached 

Is the indoor unit emitting a continu-
ous signal? 

Maintenance by authorised per-
sonnel 

The indoor unit is not  
responding to the remote 
control. 

Timer set to “ON” 

Is the timer set? 

Delete programming and wait for 
the unit to start 

Polarity of batteries incorrect after re-
placement 

Is the polarity correct? 

Insert batteries with the correct po-
larity 

Transmission distance too great / re-
ception blocked 

Is the transmission signal at a dis-
tance of approx. 3 m when the but-
ton is pressed? 

Reduce distance to under 6 m and 
change location 

Remote control defective 

Does the unit work in manual mode?  Replace remote control 

Too much direct sunlight on the re-
ceiver or transmitter 

Does the function work in the 
shade? 

Place the transmitter or receiver in 
the shade 

Electromagnetic fields are disrupting 
transmission 

Does the unit work after potential 
causes of disruption have been 
eliminated? 

No signal transmission when 
sources of disruption are operated 
simultaneously 

Remote control buttons stuck / two 
buttons pressed at once 

Does the symbol       appear on the 
display? 

Unstick button / only press one 
button 

Dead batteries in the remote control 

Are the batteries new? Is the display 
incomplete? 

Insert new batteries 

Temperature setting too high 

Is the selected temperature above 
the room temperature? 

Reduce selected temperature 

The device is either not 
cooling at all or only  
a little bit. 

Filter is dirty/ intake / outlet opening is 
blocked by foreign bodies 

Have the filters been cleaned? 

Clean filters 

Windows and doors are opened / in-
creased amount of warm air or cold air 

Have there been changes in design 
or use? 

Close the windows and doors / 
mount additional systems 

Cool mode is not set 

Does the Cool symbol (COOL) 
appear on the display? 

Correct the unit settings 

Plate fins of the outdoor part are 
blocked by foreign bodies 

Is the fan of the outdoor part work-
ing, are the plate fin exchangers 
moving freely? 

Check the fan or winter regulation 
mechanism, reduce air resistance  

Cold cycle is not leak proof 

Is there a buildup of frost visible on 
the plate fin exchangers of the in-
door unit? 

Maintenance by authorised per-
sonnel 

Condensation water 
is leaking from the  
indoor unit. 

The drainage line of the condensation 
collector is blocked / damaged  

Can condensation drain freely? 

Clean the drainage line and the 
condensation collector 

External condensation pump or float 
regulator is defective 

Is the collector filled with water and 
the pump is not working? 

Have pump checked by authorised 
service centre 

 

Before any work on the units is performed, they must be disconnected from the power supply 

(fuse or repair switch) and prevented from being inadvertently switched on

!

 

 

Содержание RKW 10 W

Страница 1: ...REMKO powerful like a bear REMKO RKV 10 W 13 W 18 W 24 W Multi purpose room air conditioners Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...n 14 Condensation Connection 15 External Condensation Pump 15 Prior to Initial Operation 17 Initial Operation 17 Environment and Recycling 18 Customer Service and Guarantee 18 Internal Wiring Diagram...

Страница 4: ...the units exclusively within the permissible operating ranges Pay attention to surrounding temperatures Make sure that the unit is kept at a safe distance from flammable materials Do not install the i...

Страница 5: ...e The difference between the point at which it switches on and off hysterisis is higher than in cooling mode 7 Temp button The temperature button can be used to set the de sired temperature in 0 5 C i...

Страница 6: ...unit to switch on or off at a later time If the room air conditioner is to be switched on at a later time press the or button for approximately 2 seconds when the unit is off In both operating modes...

Страница 7: ...ou hear a beep the COMP display begins to blink for approximately 3 minutes This waiting period is a forced pause to increase the service life of the compressor and the outdoor part Once the display s...

Страница 8: ...the filters and close the grille Maintenance and Service Shutting Down the Unit Temporary shutdown 1 Switch the indoor unit off using the remote control 2 Disconnect the system with the main switch o...

Страница 9: ...nsmission signal at a dis tance of approx 3 m when the but ton is pressed Reduce distance to under 6 m and change location Remote control defective Does the unit work in manual mode Replace remote con...

Страница 10: ...40 65 Power consumption cooling A 0 2 0 2 0 2 0 4 Current consumption max A 0 2 0 2 0 2 0 4 Supply diffuse protection recommended A See corresponding outdoor part Operating range cooling C 15 C bis 30...

Страница 11: ...oid if third party components are used Remember that when installing and maintaining air conditioners high pressure refrigerant lines and electrical current can pose hazards During unit operation some...

Страница 12: ...n and con trol lines see figure below 4 3 2 1 5 Units RKV 10 W RKV 13 W and RKV 18 W can be connected using all five options while the RKV 24 W units can only be connected using options 1 to 3 1 Outfl...

Страница 13: ...5 If you have selected Option 2 or 4 drainage through the wall guide the condensation water and control line through the wall lead through to the indoor unit If you also need a condensation pump it mu...

Страница 14: ...terminal strip of the connection towards you out of the unit Please observe the following We recommend that the customer install a main or repair switch close to the outdoor part Power is supplied to...

Страница 15: ...n If the unit is being operated at outside temperatures below 0 C the lines must be placed in such a way that they are protected from frost External Condensation Pump The condensation pump which can b...

Страница 16: ...ly The end of the ventilation hose must at least be at the same height as the con densation tray to prevent water from overflowing The supplied metal wire clips are used to secure the hose in a vertic...

Страница 17: ...values in the initial operation log Cooling operation test run Perform a test run for cooling operation as follows 1 Switch the customer installed main switch or fuse on 2 Adjust the target temperatur...

Страница 18: ...horised personnel may come into contact with the cold cycle This ensures that refrigerant does not es cape into the environment when the unit is being re paired Both the refrigerant and the system par...

Страница 19: ...tup location Name Street Postal code city Telephone Fax Testing of cycles A B C D Result Visible check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor...