background image

17 

Prior to Initial Operation 

 
After the pressure check has been performed, the vac-
uum pump must be connected to the valve connections 
of the outdoor part (see section “Impermeability Check”) 
by means of the manometer station and a vacuum cre-
ated. 

Prior to initial operation of the unit and after contact with 
the cold cycle, the following checks must be performed 
and documented in the initial operation log: 

à

Check all refrigerant lines and shut-off valves for 
leaks with a leak locator spray or soapy water. 

When the unit is not in operation. 

à

Check the connection lines to make sure that intake 
and outlet lines have not been mistakenly switched. 

à

Check the refrigerant lines and the insulation for 
damage. 

à

Check that the electrical connection between the in-
door unit and the outdoor part has the correct polar-
ity. 

à

Check all fixtures and suspended parts to ensure 
that they are in the proper position and at the correct 
height. 

 

If the refrigerant line is longer than 5 m, more re-
frigerant should be added to the system

Initial Operation 

 

Once all components have been connected and 
checked, the unit can be put into operation. Initial opera-
tion must performed using the certificate and must be 
documented. 
Following initial operation, the operator must be trained 
in its operation and the initial operation log given to him. 

 

The compressor starts a couple of minutes later 
due to the delayed start. 

4.  Check that cold air is being expelled from the indoor 

unit and warm air from the outdoor part. 

5.  During the test run, check all regulating, control and 

safety mechanisms to ensure that they are function-
ing and set properly. 

6.  Check the indoor unit’s control mechanisms using 

the functions described in the operating instructions. 

Timer, temperature settings, fan mode and dehumidi-
fying mode as well as all other mode settings. 

7. 

 Measure overheating, outside, inside, outlet and 

evaporation temperatures and enter these values in 
the initial operation log. 

Cooling operation test run 

Perform a test run for cooling operation as follows: 

1.   Switch the customer-installed main switch or fuse on. 
2.  Adjust the target temperature on the indoor unit to a 

lower value than the existing room temperature us-
ing the remote control. 

3.   Switch the unit to cooling mode with the remote con-

trol. 

Before starting the test runs, follow the instructions be-
low: 

1.   Remove the caps from the valves. 
2.  To begin initial operation, briefly open the shut-off 

valves until the manometer displays pressure meas-
uring approx. 2 bar. 

3.  Check the impermeability of all established connec-

tions with a leak locator spray or suitable devices. 

4.  If you did not find any leaks, open the shut-off valves 

by turning them all the way counter-clockwise with a 
hexagonal wrench. 

5.  If you found leaks, the connection must be re-

established.        

It is absolutely necessary to create a new vacuum 
and dry the unit!

 

The functional tests are started via the indoor unit.  

The following must be checked: 

à

Check refrigerant lines for leaks. 

à

Check that the fan and compressor are running 
smoothly. 

à

Conduct a functional test of the indoor unit and all 
program processes. 

à

Check the surface temperature of the suction line 
and determine the evaporator overheating.           

To measure the temperature, hold the thermometer on 
the suction line and subtract the boiling point tempera-
ture recorded on the manometer from the measured 
temperature.

 

Functional check and test run

 

To ensure that the unit is functioning properly, a func-
tional check must be performed to identify any irregulari-
ties during unit operation before the unit is handed over 
to the operator. 
This check is dependent on the installed outdoor part. 
These procedures are documented in the operating in-
structions of the outdoor part in use. 

Completing initial operation

 

1.  Remove the manometer and reattach all parts that 

were removed.   

Make sure that there are seals in the closing caps. 

2.   Complete the certificate for initial operation. 
3.  Familiarise the operator with the system and give 

him the filled out certificate for initial operation. 

Содержание RKW 10 W

Страница 1: ...REMKO powerful like a bear REMKO RKV 10 W 13 W 18 W 24 W Multi purpose room air conditioners Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...n 14 Condensation Connection 15 External Condensation Pump 15 Prior to Initial Operation 17 Initial Operation 17 Environment and Recycling 18 Customer Service and Guarantee 18 Internal Wiring Diagram...

Страница 4: ...the units exclusively within the permissible operating ranges Pay attention to surrounding temperatures Make sure that the unit is kept at a safe distance from flammable materials Do not install the i...

Страница 5: ...e The difference between the point at which it switches on and off hysterisis is higher than in cooling mode 7 Temp button The temperature button can be used to set the de sired temperature in 0 5 C i...

Страница 6: ...unit to switch on or off at a later time If the room air conditioner is to be switched on at a later time press the or button for approximately 2 seconds when the unit is off In both operating modes...

Страница 7: ...ou hear a beep the COMP display begins to blink for approximately 3 minutes This waiting period is a forced pause to increase the service life of the compressor and the outdoor part Once the display s...

Страница 8: ...the filters and close the grille Maintenance and Service Shutting Down the Unit Temporary shutdown 1 Switch the indoor unit off using the remote control 2 Disconnect the system with the main switch o...

Страница 9: ...nsmission signal at a dis tance of approx 3 m when the but ton is pressed Reduce distance to under 6 m and change location Remote control defective Does the unit work in manual mode Replace remote con...

Страница 10: ...40 65 Power consumption cooling A 0 2 0 2 0 2 0 4 Current consumption max A 0 2 0 2 0 2 0 4 Supply diffuse protection recommended A See corresponding outdoor part Operating range cooling C 15 C bis 30...

Страница 11: ...oid if third party components are used Remember that when installing and maintaining air conditioners high pressure refrigerant lines and electrical current can pose hazards During unit operation some...

Страница 12: ...n and con trol lines see figure below 4 3 2 1 5 Units RKV 10 W RKV 13 W and RKV 18 W can be connected using all five options while the RKV 24 W units can only be connected using options 1 to 3 1 Outfl...

Страница 13: ...5 If you have selected Option 2 or 4 drainage through the wall guide the condensation water and control line through the wall lead through to the indoor unit If you also need a condensation pump it mu...

Страница 14: ...terminal strip of the connection towards you out of the unit Please observe the following We recommend that the customer install a main or repair switch close to the outdoor part Power is supplied to...

Страница 15: ...n If the unit is being operated at outside temperatures below 0 C the lines must be placed in such a way that they are protected from frost External Condensation Pump The condensation pump which can b...

Страница 16: ...ly The end of the ventilation hose must at least be at the same height as the con densation tray to prevent water from overflowing The supplied metal wire clips are used to secure the hose in a vertic...

Страница 17: ...values in the initial operation log Cooling operation test run Perform a test run for cooling operation as follows 1 Switch the customer installed main switch or fuse on 2 Adjust the target temperatur...

Страница 18: ...horised personnel may come into contact with the cold cycle This ensures that refrigerant does not es cape into the environment when the unit is being re paired Both the refrigerant and the system par...

Страница 19: ...tup location Name Street Postal code city Telephone Fax Testing of cycles A B C D Result Visible check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor...

Страница 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: