background image

14 

Connecting the RKV 10 W, 13 W and 18 W units 

Proceed as follows to connect the units: 

1. Open the front of the unit and remove both filters. 
2. Using a Phillips screwdriver, loosen both screws of 

the grille mount and remove the grille. 

3. Remove the six screws on the front of the housing. 
4. Remember that three of the screws are hidden un-

der caps behind the oscillating blades. 

5. Remove the front cover of the housing. 
6. Pull the terminal strip of the connection towards you 

out of the unit. 

7. Connect the unit to the current-free line from the 

outer part.           

See figures.

 

8. Reassemble the unit. 

 

Prior to performing any work on the unit, it must be 
unplugged from the power supply and secured 
against being inadvertently switched on!

 

Adding Refrigerant

 

 

The refrigerant required for operating the system is lo-
cated in the outdoor part. 
For refrigerant lines longer than 5 m per cycle, refriger-
ant must be added in line with the information in the op-
erating instructions for the respective outer part. Pro-
ceed as follows to add additional refrigerant: 

1. Remove the vacuum pump and connect the filling 

cylinder. 

2. Place the open cylinder on a scale and calibrate the 

scale to zero. 

3. Create a vacuum in the hose at the height of the ma-

nometer distribution pipe. 

4. Determine the required amount based on the infor-

mation in the operating instructions of the outdoor 
part. 

5. Open the suction pressure side of the manometer. 
6. Close the manometer valve when the appropriate 

amount has been added. 

Connecting the RKV 24 W unit 

Proceed as follows to connect the unit: 

1. Open the front of the unit and remove both filters. 
2. Using a Phillips screwdriver, loosen both screws of 

the grille mount and remove the grille. 

3. Remove the five screws on the right half-shell on the 

housing. 

4. Remove the half-shell to free up the control unit on 

the right side. 

5. Pull the terminal strip of the connection towards you 

out of the unit 

Please observe the following: 

à

We recommend that the customer install a main or 
repair switch close to the outdoor part. 

à

Power is supplied to the indoor units via a connec-
tion line from the outdoor part. 

à

Fuse protection for the system must occur in accor-
dance with the technical data. 

à

The electrical terminals of the connections are lo-
cated on the lower right hand side of the indoor unit. 

 

A vacuum with a minimum of 0.05 mbar must be 
created! 

How long it takes to create the vacuum is based on the 
hose line volume of the indoor unit and the length of the 
refrigerant lines. However, this process takes a mini-
mum of 30 minutes. 
Once foreign gases and moisture have been completely 
removed from the system, the manometer station 
valves are closed and the valves of the outdoor part are 
opened as described in the section "Initial Operation“. 

Impermeability Check

 

 

Once all connections have been made, the manometer 
station is connected to the corresponding valve connec-
tions as described below: 

red     =      small valve        =    injection pressure. 
blue   =      large valve        =    suction pressure. 

After the connection has been made, an impermeability 
test is conducted using dry nitrogen. 
The connections that have been established are 
sprayed with a leak locator spray to test for imperme-
ability. Tighten the bolts more firmly or, if necessary, 
create a new flare. 
After this test has been successfully conducted, any ex-
cess pressure is removed from the refrigerant lines and 
a vacuum pump with an absolute final partial pressure 
of at least 0.01 mbar is put into operation to create a 
vacuum in the lines. This also removes any moisture 
from the lines. 

Electrical Connection 

 

A 4-wire control line must be led from the indoor unit to 
the outdoor part. All electrical installations may only be 
performed by authorised personnel in line with the rele-
vant regulations. 
Local guidelines for operation as well as the require-
ments established by local energy supply companies 
must be observed for setup and initial operation. 

Содержание RKW 10 W

Страница 1: ...REMKO powerful like a bear REMKO RKV 10 W 13 W 18 W 24 W Multi purpose room air conditioners Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...n 14 Condensation Connection 15 External Condensation Pump 15 Prior to Initial Operation 17 Initial Operation 17 Environment and Recycling 18 Customer Service and Guarantee 18 Internal Wiring Diagram...

Страница 4: ...the units exclusively within the permissible operating ranges Pay attention to surrounding temperatures Make sure that the unit is kept at a safe distance from flammable materials Do not install the i...

Страница 5: ...e The difference between the point at which it switches on and off hysterisis is higher than in cooling mode 7 Temp button The temperature button can be used to set the de sired temperature in 0 5 C i...

Страница 6: ...unit to switch on or off at a later time If the room air conditioner is to be switched on at a later time press the or button for approximately 2 seconds when the unit is off In both operating modes...

Страница 7: ...ou hear a beep the COMP display begins to blink for approximately 3 minutes This waiting period is a forced pause to increase the service life of the compressor and the outdoor part Once the display s...

Страница 8: ...the filters and close the grille Maintenance and Service Shutting Down the Unit Temporary shutdown 1 Switch the indoor unit off using the remote control 2 Disconnect the system with the main switch o...

Страница 9: ...nsmission signal at a dis tance of approx 3 m when the but ton is pressed Reduce distance to under 6 m and change location Remote control defective Does the unit work in manual mode Replace remote con...

Страница 10: ...40 65 Power consumption cooling A 0 2 0 2 0 2 0 4 Current consumption max A 0 2 0 2 0 2 0 4 Supply diffuse protection recommended A See corresponding outdoor part Operating range cooling C 15 C bis 30...

Страница 11: ...oid if third party components are used Remember that when installing and maintaining air conditioners high pressure refrigerant lines and electrical current can pose hazards During unit operation some...

Страница 12: ...n and con trol lines see figure below 4 3 2 1 5 Units RKV 10 W RKV 13 W and RKV 18 W can be connected using all five options while the RKV 24 W units can only be connected using options 1 to 3 1 Outfl...

Страница 13: ...5 If you have selected Option 2 or 4 drainage through the wall guide the condensation water and control line through the wall lead through to the indoor unit If you also need a condensation pump it mu...

Страница 14: ...terminal strip of the connection towards you out of the unit Please observe the following We recommend that the customer install a main or repair switch close to the outdoor part Power is supplied to...

Страница 15: ...n If the unit is being operated at outside temperatures below 0 C the lines must be placed in such a way that they are protected from frost External Condensation Pump The condensation pump which can b...

Страница 16: ...ly The end of the ventilation hose must at least be at the same height as the con densation tray to prevent water from overflowing The supplied metal wire clips are used to secure the hose in a vertic...

Страница 17: ...values in the initial operation log Cooling operation test run Perform a test run for cooling operation as follows 1 Switch the customer installed main switch or fuse on 2 Adjust the target temperatur...

Страница 18: ...horised personnel may come into contact with the cold cycle This ensures that refrigerant does not es cape into the environment when the unit is being re paired Both the refrigerant and the system par...

Страница 19: ...tup location Name Street Postal code city Telephone Fax Testing of cycles A B C D Result Visible check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor...

Страница 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: