Press the
key for two seconds. If the error code continues to display,
search for the cause in the error table and apply the solution.
Note
If the display does not show
but rather , the boiler must be
switched off and then switched on again 10 seconds later before
the error can be reset.
Tab.32 Error codes
Error code
Description
Possible cause
Check/solution
Parameter storage unit PSU
not found
Bad connection
Check the wiring
Safety parameters not OK
Bad connection
Defective PSU
Check the wiring
Replace PSU
Flow temperature sensor
short circuited
Bad connection
Sensor failure
Sensor not connected or in
correctly connected
Check the wiring
Check that the sensors are operating cor
rectly
Check that the sensor has been fitted prop
erly
Replace the sensor if necessary
Flow temperature sensor
open
Bad connection
Sensor failure
Sensor not connected or in
correctly connected
Check the wiring
Check that the sensors are operating cor
rectly
Check that the sensor has been fitted prop
erly
Replace the sensor if necessary
Temperature of heat ex
changer too low
Temperature of heat ex
changer too high
Bad connection
Sensor failure
Sensor not connected or in
correctly connected
No flow
Check the wiring
Replace the sensor if necessary
Vent the central heating system
Check the flow (direction, pump, valves)
Check the water pressure
Check that the sensors are operating cor
rectly
Check that the sensor has been fitted prop
erly
Check the cleanliness of the heat exchang
er
If present: check setting of boiler type pa
rameter
Return temperature sensor
short-circuited
Bad connection
Sensor failure
Sensor not connected or in
correctly connected
Check the wiring
Check that the sensors are operating cor
rectly
Check that the sensor has been fitted prop
erly
Replace the sensor if necessary
Open circuit in return temper
ature sensor
Bad connection
Sensor failure
Sensor not connected or in
correctly connected
Check the wiring
Check that the sensors are operating cor
rectly
Check that the sensor has been fitted prop
erly
Replace the sensor if necessary
11 Troubleshooting
66
123157 - v.06 - 24022015