4. If the measured value is outside of the values given in the table, cor
rect the gas/air ratio.
5. Using adjusting screw A, adjust the percentage of O
2
/CO
2
for the
gas type being used to the nominal value. This should always be in
side the highest and lowest setting limit.
6. The O
2
/CO
2
value set at full load has a corresponding set value at
low load (see table). Make a note of the full load value set and use
this for setting at low load.
Checking/setting values for O
2
/CO
2
at low load
1. Set the boiler to low load. Press the key several times until
appears on the display.
2. Measure the percentage of O
2
/CO
2
in the flue gases.
3. Compare the measured value with the checking values in the table.
Tab.25 Checking/setting values O
2
/CO
2
at low load for G20 (H gas)
Values at low load for G20 (H
gas)
O
2
(%)
CO
2
(%)
Quinta Pro 30
5.7
(1)
– 6.2
8.2 – 8.5
(1)
Quinta Pro 45
5.7
(1)
– 6.2
8.2 – 8.5
(1)
Quinta Pro 65
4.8
(1)
– 5.3
8.7 – 9.0
(1)
Quinta Pro 90
4.8
(1)
– 5.3
8.7 – 9.0
(1)
Quinta Pro 115
5.6
(1)
– 6.1
8.3 – 8.6
(1)
(1) Nominal value
Tab.26 Checking/setting values O
2
/CO
2
at low load for G31 (pro
pane)
Values at low load for G31 (pro
pane)
O
2
(%)
CO
2
(%)
Quinta Pro 30
5.4
(2)
– 5.9
9.9 – 10.2
(2)
Quinta Pro 45
5.4
(1)
– 5.9
9.9 – 10.2
(2)
Quinta Pro 65
5.4
(2)
– 5.9
10.1 – 10.4
(2)
Quinta Pro 90
5.4
(2)
– 5.9
9.9 – 10.2
(2)
Quinta Pro 115
5.7
(2)
– 6.2
9.7 – 10.0
(2)
(1) Nominal value
Caution
The O
2
values at low load must be higher than the O
2
values at
full load.
The CO
2
values at low load must be lower than the CO
2
values
at full load.
4. If the measured value is outside of the values given in the table, cor
rect the gas/air ratio.
Fig.39 Position of adjusting screw A
AD-0000067-01
A
A
Fig.40 Setting to low load
AD-0000071-01
rpm
kWµA
± 30
l/min
bar
Psi
St
ºC
ºCºFh
7 Commissioning
123157 - v.06 - 24022015
43