Blocking code Description
Possible cause
Check/solution
Blocking input is active
External cause
Parameter error
Bad connection
Remove external cause
Check parameters
Check the wiring
Blocking input active or frost
protection active
External cause
Parameter error
Bad connection
Remove external cause
Check parameters
Check the wiring
Communication error with the
SCU PCB
Poor connection with BUS
SCU PCB not present in
boiler
Check the wiring
Carry out automatic detection
Water pressure too low
Water pressure too low
Check the water pressure
Fill the boiler and the installation with water
Gas pressure too low
No flow or insufficient flow
Incorrect setting on gas
pressure switch (Gps) on
SCU PCB
Check that the gas valve is fully opened
Check the gas supply pressure
Check whether the Gps has been correctly
fitted
Replace the Gps switch if necessary
(1)
Configuration error or SU
PCB not recognised
Incorrect SU PCB for this boil
er
Replace SU PCB
(1)
Configuration error or default
parameter table incorrect
Parameter error in the PCU
PCB
Replace PCU PCB
(1)
Configuration error or PSU
PCB not recognised
Incorrect PCU PCB for this
boiler
Replace PCU PCB
(1)
Configuration error or param
eters
and
unknown
-
Reset
and
(1)
Configuration procedure ac
tive
Active for a short time after
switching on the boiler
No action
Communication error with the
SU PCB
Bad connection
Check whether the PCU PCB has been cor
rectly fitted in the connector on the SU PCB
No flame during operation
No ionisation current
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check that the air supply inlet and flue gas
outlet are not blocked
Check that there is no recirculation of flue
gases
Internal error in SU PCB
-
Replace SU PCB
(1) These blocks are not stored in the error memory
11.1.2 Lock out
If the blocking conditions still exist after various start attempts, the boiler
goes into lockout (also called error). The boiler will also lock out if an error
is signalled anywhere in the boiler. An error code will appear on the dis
play. The error code is displayed as follows:
In a red flashing display:
the symbol
the symbol
the error code, for example
The meaning of the error codes can be found in the error table. Note the
error code.
Note
The error code is needed to find the cause of the error quickly and
correctly and for any support from Remeha.