9 Settings
9.1 Parameter descriptions
Tab.27 Factory setting
Parame
ter
Description
Adjustment range
30
45
65
90
115
Flow temperature: T
SET
20 to 90ºC
80
80
80
80
80
DHW temperature: T
SET
40 to 65ºC
55
55
55
55
55
Boiler control/DHW
0 = CH off/DHW off
1 = CH on/DHW on
2 = CH on/DHW off
3 = CH off/DHW on
1
1
1
1
1
ECO setting
0 = Comfort
1 = ECO setting
2 = Controller dependent
2
2
2
2
2
Anticipation resistance
0 = No anticipation resistance
for the ON/OFF thermostat
1 = Anticipation resistance for
the ON/OFF thermostat
0
0
0
0
0
Display screen
0 = Simple
1 = Extended
2 = Automatic switching to
simple after three minutes
3 = Automatic switching to
simple after three minutes;
key lock is active
2
2
2
2
2
Post-circulation of the pump
1 to 98 minutes
99 minutes = continuous
3
3
3
3
3
Brightness of display lighting
0 = Dimmed
1 = Bright
1
1
1
1
1
Maximum fan speed (central heating) G20 (H gas) x100 rpm
41
56
58
62
70
Maximum fan speed (DHW)
G20 (H gas) x100 rpm
41
56
58
62
70
Minimum fan speed (CH + DHW)
G20 (H gas) x100 rpm
15
15
16
17
18
Minimum fan speed (offset)
50
50
0
0
0
Start speed
25
25
25
25
25
Minimum water pressure
0–3 bar (x 0.1 bar)
8
8
8
8
8
Maximum flow temperature of system 0 to 90°C
90
90
90
90
90
Reserve
-
-
-
-
-
Heat curve set point
(Maximum outside temperature)
0 to 30ºC
(1)
20
20
20
20
20
Heat curve set point
(Flow temperature)
0 to 90ºC
(1)
20
20
20
20
20
Heat curve set point
(Minimum outside temperature)
-30 to 0ºC
(1)
-15
-15
-15
-15
-15
Setting the pump speed
(Minimum pump speed for central
heating operation)
2–10 (x 10%)
4
4
4
4
4
Setting the pump speed
(Maximum pump speed for central
heating operation)
2–10 (x 10%)
10
10
10
10
10
Frost protection temperature
-30 to 0ºC
-10
-10
-10
-10
-10
9 Settings
46
123157 - v.06 - 24022015