Room-sealed version (C13, C33, C43, C63, C93)
Flue gas outlet connection
Air supply connection
With a closed version, both the flue gas outlet and the air supply openings
are connected (concentrically).
Tab.12 Maximum chimney length (L)
Quinta Pro
Diameter
80–125 mm
100–150 mm
30
20 m
20 m
45
16 m
20 m
65
-
13 m
90
-
13 m
115
-
7 m
Connection in different pressure areas (C53, C83)
Flue gas outlet connection
Air supply connection
A 100/100 mm flue gas adapter (accessory) must be fitted for this connec
tion.
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Tab.13 Maximum chimney length (L) in the various pressure zones
Quinta Pro
Diameter
80 mm
90 mm
100 mm
110 mm
130 mm
30
20 m
36 m
36 m
36 m
36 m
45
20 m
36 m
36 m
36 m
36 m
65
-
2 m
8 m
34 m
36 m
90
-
-
4 m
32 m
36 m
115
-
-
-
24 m
36 m
Reduction table
Tab.14 Pipe reduction for each element used (parallel)
Diameter
Pipe reduction
45° bend
90° bend
60 mm
0.9 m
3.1 m
70 mm
1.1 m
3.5 m
80 mm
1.2 m
4.0 m
90 mm
1.3 m
4.5 m
100 mm
1.4 m
4.9 m
110 mm
1.5 m
5.4 m
130 mm
1.6 m
6.2 m
Fig.14 Room-sealed version (concentric)
AD-0000029-01
L =
Fig.15 Different pressure areas
AD-0000030-01
L =
+