Connection options for the 0–10 V PCB (IF-01)
The IF-01 PCB can be built into the instrument box or the housing for the
PCBs. See the instructions provided with the product.
Caution
Do not connect a frost thermostat or room thermostat to the boiler
if using the 0–10 V PCB.
Connecting the status relay (Nc)
If the boiler locks out, a relay is de-energised and the alarm can be trans
mitted via a potential-free contact (maximum 230 V, 1 A) on terminals Nc
and C of the connector.
Connection (OTm)
The interface uses OpenTherm to communicate with the boiler control
unit. To make this possible, the OTm connection must be connected to the
OpenTherm input of the boiler control unit.OTm
Analogue input (0-10 V)
A choice can be made with this control between control based on temper
ature or heat output. The two controls are described briefly below.
1. Connect the input signal to terminals 0–10 of the connector.
Tab.21 Temperature-based control (°C)
Jumper 2 Input signal (V)
Temperature °C Description
0–1.5
0–15
Boiler off
1.5–1.8
15–18
Hysteresis
1.8–10
18–100
Desired temperature
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
A jumper (2) on the interface is used to select either temperature-based
control ( ) or output-based control (%).
Tab.22 Control based on heat output
Jumper 2 Input signal (V)
Heat output (%) Description
%
0–20
Boiler off
20–22
Hysteresis
2.0–10
20–100
Desired heat output
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
The 0–10 V signal controls the boiler output. This control modulates on the
basis of the heat output. The minimum output is linked to the boiler's mod
ulation depth. The output varies between the minimum and maximum val
ue on the basis of the value defined by the controller.
Fig.31
IF-01 PCB
AD-0000054-01
St
a
tu
s
0
-1
0
0
-1
0
N
c
N
o
C
N
c
N
o
O
T
m
0
+
0
+
C
O
T
m
0
+
0
+
X5
X4
X1
IF-01
%
1
2
Fig.32
Switch jumper (2)
AD-0000055-01
1
2
%
2
2
6 Installation
38
123157 - v.12 - 07022018
Содержание Quinta Pro 115
Страница 86: ...14 Appendix 86 123157 v 12 07022018 ...