4 Description of the product
4.1
General description
The Quinta Pro boiler has the following characteristics:
High-efficiency heating.
Limited emissions of polluted substances.
Ideal choice for cascade configurations.
Option to produce domestic hot water using a separate hot water appli
ance.
4.2
Operating principle
4.2.1
Circulating pump
Model not supplied with circulating pump
The boiler is supplied without a pump. Take the boiler resistance and sys
tem resistance into account when selecting a pump.
Caution
The pump may have a maximum input of 200 W. Use an auxiliary
relay for a pump with greater power.
See
If possible, install the pump directly under the boiler on the return connec
tion.
For more information, see
Connecting the heating circuit, page 23
Pump settings
The pump settings for a modulating circulating pump controlled by the
control unit can be modified using parameters
and
:
If there is insufficient flow in the radiators or if they do not warm up com
pletely, the minimum pump speed can be increased using parameter
.
If there are audible flowing noises in the system, the maximum pump
speed must be lowered using parameter
(bleed the CH installa
tion first).
Caution
The pump may have a maximum input of 200 W. Use an auxiliary
relay for a pump with greater power.
For more information, see
Changing the parameters at installer level, page 54
4.2.2
Cascade system
The boiler is ideally suited for a cascade system. There are a number of
standard solutions available.
Important
Contact us for more information.
4.2.3
Water flow
The modulating control of the boiler limits the maximum temperature differ
ence between the flow and return and the maximum rise velocity of the
4 Description of the product
18
123157 - v.12 - 07022018
Содержание Quinta Pro 115