Diameter
80 mm
90 mm
100 mm
110 mm
130 mm
(1) Retaining the maximum chimney length, it is possible to use an extra 5 x 90º or 10 x 45º elbows.
Room-sealed model (C
13(X)
, C
33(X)
, C
63(X)
)
Connecting the flue gas outlet
Connecting the air supply
With a room-sealed version, both the flue gas outlet and the air supply
openings are connected (concentrically).
Tab.16 Maximum chimney length (L)
Diameter
80/125 mm
100/150 mm
Quinta Pro 30
20 m
Quinta Pro 45
20 m
Quinta Pro 55
8 m
Quinta Pro 65
4 m
18 m
Quinta Pro 90
4 m
17 m
Quinta Pro 115
-
13 m
(1) Retaining the maximum chimney length, it is possible to use an extra 5 x
90º or 10 x 45º elbows.
Connection in different pressure areas (C
53(X)
)
L Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
A 100/100 mm flue gas adapter (accessory) must be fitted for this connec
tion.
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Tab.17 Maximum length (L)
Diameter
80 mm
90 mm
100 mm
110 mm
130 mm
Quinta Pro 30
17 m
29 m
40 m
40 m
Quinta Pro 45
29 m
40 m
40 m
Quinta Pro 55
9 m
17 m
27 m
40 m
Quinta Pro 65
5 m
10 m
16 m
34 m
Quinta Pro 90
-
-
17 m
37 m
Quinta Pro 115
-
-
14 m
31 m
(1) Retaining the maximum chimney length, it is possible to use an extra 5 x 90º or 10 x 45º elbows.
Fig.15
Room-sealed version (concentric)
AD-0000029-02
L =
Fig.16
Different pressure areas
AD-0000030-02
=
L
+
6 Installation
28
123157 - v.12 - 07022018