10 Maintenance
10.1 General
The boiler does not require a lot of maintenance. Nevertheless, the boiler
must be inspected and maintained periodically. To determine the best time
for servicing, the boiler is equipped with an automatic service message.
The control unit determines when this service message appears. Depend
ing on boiler use, the first service message appears no later than 3 years
after installation of the boiler.
Caution
Maintenance operations must be completed by a qualified in
staller.
During inspection or maintenance work, always replace all gas
kets of the disassembled parts.
We recommend taking out a maintenance contract.
Replace defective or worn parts with original spare parts.
An annual inspection is mandatory.
10.2 Maintenance message
The boiler display will clearly indicate that a service is required at the ap
propriate time. Use the automatic maintenance message for preventive
maintenance, to keep faults to a minimum. The service messages show
which service kit must be used. These service kits contain all parts and
gaskets that are required for the relevant service. These service kits (A, B
or C), put together by Remeha, are available from your spare parts suppli
er.
Important
A maintenance message must be followed up within 2 months.
Therefore, call your installer as soon as possible.
Important
If the iSense modulating thermostat is connected to the boiler, this
thermostat can also display the maintenance message. Consult
the thermostat manual.
Caution
Reset the maintenance message following every service.
10.2.1 Resetting the service messages
A service message on the boiler display must be reset by a qualified in
staller after the maintenance service has been carried out using the rele
vant service kit. Proceed as follows:
1. When the maintenance message is displayed, press the
key
once.
appears on the display.
2. Use the or keys to set the installer code
.
3. Confirm by pressing the
key.
The maintenance message is reset. The display returns to the cur
rent operating mode.
Fig.59
Setting the installer code
AD-0000081-01
1x
10 Maintenance
62
123157 - v.12 - 07022018
Содержание Quinta Pro 115
Страница 86: ...14 Appendix 86 123157 v 12 07022018 ...