10.3.2 Checking the ionisation current
1. Check the ionisation current at full load and at low load.
The value is stable after 1 minute.
2. Clean or replace the ionisation/ignition electrode if the value is lower
than 4 µA.
For more information, see
Replacing the ionisation/ignition electrode, page 67
10.3.3 Checking the flue gas outlet/air supply connections
1. Check the flue gas outlet and air supply connections for condition
and tightness.
10.3.4 Checking the combustion
Combustion is checked by measuring the O
2
/CO
2
percentage in the flue
gas outlet duct.
For more information, see
Checking and setting the gas/air ratio, page 45
Fig.61
Checking flue gas outlet/air supply
connections
AD-0000084-01