For more information, see
Replacing the ionisation/ignition electrode, page 71
10.3.4 Check the flue gas outlet/air supply connections
1. Check the flue gas outlet and air supply connections for condition and
tightness.
10.3.5 Checking the combustion
Combustion is checked by measuring the O
2
/CO
2
percentage in the flue
gas outlet duct.
10.3.6 Checking the PS air pressure differential switch
Checking the air pressure differential side
1. Switch off the boiler.
2. Disconnect the silicon hose on the + side (P1) of the air pressure
differential switch.
3. Take a large plastic syringe or bellows and connect a T piece with a
hose connected.
4. Connect the + side of the air pressure differential switch to one end of
the T piece with a hose.
5. On the other end of the T piece, connect the + side of a pressure
gauge.
6. Turn on the boiler
7. Push the syringe or bellows in very slowly until the boiler goes into
failure mode.
8. Make a note of the pressure indicated by the pressure gauge at that
point. A switch pressure of between 5.5 and 6.5 mbar is fine. A lower
or higher switch pressure indicates a problem with the air pressure
differential switch.
9. After taking a measurement, detach the silicon hose from the T piece
on the + side and reconnect the hose that was previously removed.
Caution
Please note: The + side (P1) is the rear connector nipple of the air
pressure differential switch.
10. Remove any soiling from all connection points for hoses and the air
pressure differential switch.
11. Check the condition and tightness of the hoses of the air pressure
differential switch. Replace the hoses if necessary.
Fig.83
Check the air pressure differential
side
AD-0001181-01
SLOW
(+)
7
3
5
X mbar
....
....
m
ba
r
5,5 mbar.... 6,5
8
P
1
(+)
P
2
(-)
2
9
4
1
6
10 Maintenance
64
7665063 - v.05 - 18102018