1. Fill the siphon with water up to the mark.
2. Push the siphon firmly into the designated opening
behind the
cover underneath the boiler and connect the siphon hose.
3. Push the retainer clip of the siphon forwards.
4. Check whether the siphon is firmly fitted in the boiler.
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
6.7.3
Filling the system
Important
In order to be able to read off the water pressure from the control
panel, the boiler must be switched on. If the water pressure is too
low, the boiler or the boiler pump will not start.
1. Fill the central heating system with clean tap water.
Important
The recommended water pressure is between 1.5 and 2 bar.
2. Check the water-side connections for tightness.
Fig.49
Fill the siphon
AD-4100153-01
4
1
2
3
6 Installation
44
7665063 - v.05 - 18102018