6.5.6
Connecting the flue gas outlet
S Insertion depth 30 mm
1. Fit the flue gas outlet pipe to the boiler.
2. Fit the successive flue gas outlet pipes seamlessly together.
Caution
The pipes must be flue gas-tight and corrosion-resistant.
The flue gas outlet pipe must be smooth and deburred.
Connect the pipes so that they are stress-free.
The pipes must not rest on the boiler.
Fit the horizontal parts sloping down towards the boiler, with a
slope of 50 mm per metre.
6.5.7
Connecting the air supply
S Insertion depth 30 mm
1. Fit the air supply pipe to the boiler.
2. Fit the successive air supply pipes seamlessly together.
Caution
The pipes must be airtight and corrosion-resistant.
The air supply pipe must be smooth and deburred.
Connect the pipes so that they are stress-free.
The pipes must not rest on the boiler.
Fit the horizontal parts sloping down towards the air supply
outlet.
Fig.30
Connecting the flue gas outlet
AD-0001172-01
S
Ø150 mm
Fig.31
Connecting the air supply
AD-0001173-01
S
Ø150 mm
6 Installation
36
7665063 - v.05 - 18102018