10.3.10 Clean the condensate collector
1. Remove the air intake silencer.
2. Remove the sealing cap from the condensate collector.
3. Rinse the condensate collector thoroughly with a water flow that is as
large as possible.
Warning
When flushing, prevent water from getting into the boiler.
4. Disconnect the silicon hose of the air pressure differential switch from
the connection nipple on the condensate collector.
5. Clean the opening of the connection nipple thoroughly (by blowing air
or pushing an object through it).
6. Reconnect the silicon hose.
7. Put the air intake silencer and the sealing cap back on the condensate
collector.
10.3.11 Cleaning the siphon
1. Pull the retainer clip of the siphon backwards.
2. Carefully pull the siphon and siphon hose downwards.
3. Clean the siphon with water.
4. Fill the siphon with water up to the mark.
5. Push the siphon firmly into the designated opening
behind the
cover underneath the boiler and install the siphon hose.
6. Push the retainer clip of the siphon forwards.
7. Check whether the siphon is firmly fitted in the boiler.
Danger
The siphon must always be filled with water. This prevents flue
gases from entering the room.
10.4 Specific maintenance work
Perform the specific maintenance work if this proves to be necessary
following the standard inspection and maintenance work. To conduct the
specific maintenance work:
Fig.89
Clean the condensate collector
AD-0001186-02
2
3
1
Fig.90
Cleaning the siphon
AD-4100152-01
1
2
3
7
5
6
4
10 Maintenance
70
7665063 - v.05 - 18102018