E L E C T R I C A L I N S TA L L AT I O N I N S T R U C T I O N S
Warning:
When installing or using electrical products, basic precautions should always be followed, including:
1. All Reliance whirlpool and air baths require a separate 15 amp 110VAC circuit for each pump
or air system blower. The inline heater for whirlpools adds 5.3 amps. The inline heater for
air baths and soakers (HTISOAK) will require an additional 20 amp circuit. This circuit must
be connected to a supply that is protected by a ground fault circuit interrupter (GFCI). Such
a GFCI should be provided by the installer and tested on a routine basis. To test the GFCI,
push the test button. The GFCI should interrupt power. Push the reset button. Power should
be restored. If the GFCI fails to operate in this manner, there is a ground current flowing, indi-
cating the possibility of electric shock. Do not use this unit. Disconnect the unit and have the
problem corrected by a qualified electrician before using.
2. Every Reliance whirlpool or air bath is supplied with a 29” grounded plug on each pump,
inline heater or air blower to be plugged into a standard grounded receptacle. Do not remove
this plug. If a wall mount switch is desired to control use of the unit, the switch should control
the receptacle. Under no circumstance should you alter the provided supply cord.
3.
A pressure wire connector is supplied on the exterior of the pump to permit connection
of a No.8AWG (8.4mm) solid copper bonding conductor between this unit and all other
electrical equipment and exposed metal in the vicinity as needed to comply with local
requirements. NOTE: air blowers do not require a bonding conductor.
110VAC
Power
Supply
See Manufacturers Wiring Diagram on Motor
Grounding Conductor
(Pressure Wire Connector)
GFCI
Motor
Green/Ground
White/Neutral
Black/Hot