54
REGULUS SRS6 EP Controller - www.regulus.eu
J. - Appendix - Pump control - types
Manual pump settings (see “6.2. - Pump menu“)
J. 14.1. Pump
Settings for various pump models.
J. 14.2. - Output Signal
This menu determines the type of pump used:
Solar pumps perform at their highest power when the signal is also at its max, heating
pumps on the other hand are set to highest power when the control signal is at the lowest.
Solar = normal, heating = Inverted.
Settings range: Normal, Inverted / Default setting: Normal
J. 14.3. - PWM off
This signal is put out when the pump is switched off (pumps that can detect cable break
need a minimum signal).
Settings range: (Solar:) 0 to 50% / Default setting: 0% - Heating:) 50% to 100%/Default set-
ting: 100%
J. 14.4. - PWM on
This signal is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0 to 50% / Default setting: 10% - (Heating:) 50% to 100% / Default
setting: 90%
J. 14.5. - PWM Max
This determines the output signal for the highest speed of the pump, that is used e.g. during
purging or manual operation.
Settings range: (Solar:) 50 to 100% / Default setting: 100% - (Heating:) 0% to 50% / Default
setting: 0%
J. 17.3. - 0-10V Off
This voltage is put out when the pump is turned off (pumps that can detect cable break
need a minimum voltage).
Settings range:(Solar:) 0,0 to 5,0 V /Default setting: 1.0 V - (Heating:) 5.0 to 0.0 V /Default
setting: 4.0 V
J. 17.4. - 0-10V On
This voltage is needed to turn the pump on at minimum speed.
Settings range:(Solar:) 0.0 to 5.0 V/Default setting:1.0 V - (Heating:) 5.0 to 10.0 V/Default
setting: 9.0 V
J. 17.5. - 0-10V Max
This determines the output voltage for the highest speed of the pump, that is used e.g. du-
ring purging or manual operation.
Settings range:(Solar:) 5.0 to 10.0 V /Default setting: 10.0 V- (Heating:) 0.0 to 5.0V/Default
setting: 0.0 V
J. 17.6. - Speed when “On“
This menu determines the calculated and displayed speed of the pump. If e.g. 30% is set
here and the signal set in „PWM on/0-10V on“ is put out, 30% speed is displayed. When
the signal set in „PWM max/0-10V max“ is put out, 100% speed is displayed. Everything in
between is calculated accordingly.
Settings range: 10 to 90 % / Default setting: 30 %
Caution:
This function has no in
fl
uence on the regulation, but changes only the
speed displayed.
J. 14.7. - Show signal
Displays the set signal in text and a graphical diagram.
Caution