Special functions
menu 6
6.3.4 Max. speed
menu 6.3.4
The maximum speed of the pump is speci
fi
ed here
Settings range: 70-100% / Default setting: 100%
The indicated percentages are guide values that may vary to a greater or lesser extent depending on the sys-
tem, pump and pump stage.
6.3.5 Min. speed
menu 6.3.5
The minimum speed of the pump at relay R1 is speci
fi
ed here.
Settings range: from (see J.14.6. - Speed when „On“ on page 53) to max. speed -5 % / Default setting: 50%
The indicated percentages are guide values that may vary to a greater or lesser extent depending on the sys-
tem, pump and pump stage. 100% is the maximum possible for the existing voltage/ frequency of the control-
ler.
6.3.6 Setpoint
menu 6.3.6
This value is the control setpoint for Mode 3 (see „6.3.1. - Modes“ on page 31). If the value at the collector
sensor drops below this, the speed is reduced. If it rises above this, the speed is increased.
Settings range: 0 - 90 °C / Default setting: 60 °C