REGULUS SRS6 EP Controller - www.regulus.eu
Settings
menu 4
4 - Settings
The system parameters are set in menu
“4. Settings”
.
The menu is closed by pressing
“esc”
or selecting
“Exit settings”
.
Various settings can be made depending on the selected hydraulic variant.
In many cases more conditions shall be met at one time in order to close the relay, see the setting tables. (E.g.
Δ
T between a collector and a storage tank, min./max. collector temperature and max. storage tank temperatu-
re.) The relay will not close when only one condition is met (e.g.
Δ
T has been reached but the collector has not
reached the T1min temperature).
4.1 - Tmin S(X)
menu 4.x
= Sensor S
(X)
switch-on temperature at sensor
S(X)
If the temperature at sensor S1 exceeds the value of TminS
(X)
and the other conditions in the Table are also
met, then the controller switches on the associated pump and/or valve. If the temperature at the sensor S1
drops below the value of TminS
(X)
by 5°C, then the pump and/or the valve are switched off again.
Settings range: 0-99 °C / Default setting: 20 °C
4.2 - Tmax S(X)
menu 4.x
= Sensor S
(X)
switch-off temperature at sensor
S(X)
If the temperature at sensor S
(X)
exceeds the value of TminS
(X)
and the other conditions in the Table 4.14 are
also met, then the controller switches on the associated pump and/or valve. If the temperature at the sensor
S(X) drops below the value of TmaxS
(X)
, then the pump and/or the valve are switched off again.
Settings range: 0-99 °C / Default setting: 60 °C
Temperature values which are set high will allow higher solar heat accumulation but it shall be
checked that all system components are resistant to high temperatures and scalding protection is
provided. Regulus solar systems are safe for heating water up to 95 °C.
4.3 - Tmax SB
menu 4.x
= Switch-off temperature at pool sensor
If this value is exceeded at the applicable sensor, the controller switches the associated pump and/or valve off.
If the temperature falls below TmaxSB again, then the controller switches the pump and/or valve on again.
Settings range: 0-50 °C / Default setting: 28 °C
Caution
Danger