46
REGULUS SRS6 EP Controller - www.regulus.eu
Special functions
menu 6
6.5.2. – VFS (X)
menu 6.5.2
6.5.2.1 – VFS Type
menu 6.5.2.1
The VFS type is set here
Settings range: Off; 1-12; 1-20; 2-40; 5-100; 10-200; 20-400 / Default setting: Off
6.5.2.2. - VFS - Position
menu 6.5.2.2
This setting determines the position of the VFS
fl
owmeter with temperature sensor.
Settings range:
fl
ow, return / Default setting: return
Warning:
To prevent damage to the Vortex Flow Sensor it is strongly recommended to install it into the return
fl
ow. If it is necessary to install in the
fl
ow, it is imperative not to exceed the maximum temperatures
of the sensor! (0° C to 100 °C and -25 °C to 120 °C short term.)
6.5.2.3. – Reference sensor
menu 6.5.2.3
The reference sensor used for the heat metering is set here.
Settings range: S1-S8, VFS1-2, active collector, active storage/ Default setting: S1
-----------------------------------------------------------------------------------
6.6. - Pressure monitor
menu 6.6
A message is shown when the pressure drops below set minimum or exceeds the set maximum pressure. No
relay is switched, for that see „6.4.12. - Pressure monitor“ on page 43.
6.6.1. - Pressure monitor
menu 6.6.1
A message is shown and the LED
fl
ashes when the pressure deviates from the set minimum or maximum
value.
Default setting: On, Off / Výchozí nastavení: Off
6.6.1.1. - RPS1 / RPS2
menu 6.6.1.1
Type of pressure sensor
This menu is used to determine the type of pressure sensor used.
Please note:
If e.g. VFS1 is connected, RPS1 option is not shown.
Settings range: Off; 0-0.6 bar; 0-1 bar; 0-1.6 bar; 0-2.5 bar; 0-4 bar; 0-6 bar; 0-10 bar
Default setting: Off
6.6.1.2.
–
Pmin
menu 6.6.1.2
Minimum pressure
If this value is undershot, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 to 1.6 bar
Default setting: 0,0bar
6.6.1.3.
-
Pmax
menu 6.6.1.3
Maximum pressure
If this value is exceeded, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 to 10 bar
Default setting: 1.6 bar
Danger