Special functions
menu 6
6 - Special functions
Menu
“6. Special functions”
is used to set basic
items and expanded functions.
Time and Date is the only function to be
set by the user. Other functions may be
set by a specialist only.
The menu is closed by pressing “esc” or selecting
“Exit special functions”.
Menu numbering depends on the hydraulic variant selected
6. 1 - Program selection
menu 6.1
The suitable hydraulic variant for the speci
fi
c application is selected and set here (see Chapter D2 Hydraulic
variants, page 13). The associated diagram can be displayed by pressing “info”.
Settings range: Program selection: 1-37 / Default setting: 1
Normally the program selection is made only once during initial commissioning by the specialist.
Incorrect program selection can lead to wrong operation and unpredictable errors. Once the pro-
gram is changed, other settings are reset to factory values.
6. 2 - Signal V1 (V2)
menu 6.2
Setting for high ef
fi
ciency pumps with either 0-10V or PWM control.
High ef
fi
ciency pumps with either 0-10V or PWM control shall be connected to the respective relay
(V1 to R1, R2 to V2). Relays are switched on/off together with the 0-10V / PWM control signal.
6.2.1 Type of pump
menu 6.2.1
Standard:
enables speed control for standard pump
0-10V:
enables speed control for high ef
fi
ciency pumps with 0-10V control
PWM:
enables speed control for high ef
fi
ciency pumps with PWM control.
6.2.2 Pump
menu 6.2.2
In this menu, precon
fi
gured pro
fi
les for pump control can be selected.
Described in Chapter J - Appendix.