Information for the specialist - Configuration
Summer mode
Table 4-26 Settings for Summer mode
Variable
Read/Write
Default
value
Min/Max
Note
Date for start of summer period
W
1
1/31
Month for start of summer period
W
4
1/12
Date for end of summer period
W
1
1/31
Month for end of summer period
W
10
1/12
Outdoor temp for switch between
summer / winter (°C)
W
13
0/99
Outdoor temp hysteresis for switch
between summer / winter (°C)
W
0,5
0/99
4.4.3
Fan control
Ventilation
Fan control
Fans
Supply air fan
Extract air fan
Fan comp. curve
Fans
Table 4-27 Settings for fans
Variable
Read/Write
Default
value
Min/Max
Note
Offset supply air fan when free
cooling (%)
W
0
-100/100
Offset extract air fan when free
cooling (%)
W
0
-100/100
Supply air fan
Table 4-28 Settings for supply air fan
Variable
Read/Write
Default
value
Min/Max
Note
Start delay (s)
W
60
0/3600
Stop delay (s)
W
180
0/3600
Outdoor air damper stop delay (s)
W
0
0/3600
SAF speed min limit (%)
W
0
0/100
SAF speed max limit (%)
W
100
0/100
Optigo
Ardo
manual, Rev. A
49 (76)