Information for the specialist - Configuration
Extract air fan
Table 4-29 Settings for extract air fan
Variable
Read/Write
Default
value
Min/Max
Note
Start delay (s)
W
0
0/3600
Stop delay (s)
W
30
0/3600
Outdoor air damper stop delay (s)
W
0
0/3600
EAF speed min limit (%)
W
0
0/100
EAF speed max limit (%)
W
100
0/100
Fan compensation curve
Table 4-30 Settings for fan compensation curve
Variable
Read/Write
Default
value
Min/Max
Note
Lower point X
W
15
-30000/
30000
Lower point Y (%)
W
0
-100/100
Middle point X
W
20
-30000/
30000
Middle point Y (%)
W
0
-100/100
Higher point X
W
25
-30000/
30000
Higher point Y (%)
W
0
-100/100
4.4.4
Demand control
Ventilation
Demand control
CO2
Free cooling
Support control
CO2
Table 4-31 Settings for CO2
Variable
Read/Write
Default
value
Min/Max
Note
Start limit fan start/stop (ppm)
W
800
0/2000
Stop hysteresis fan start/stop (ppm) W
160
0/2000
Demand control
R
Min time for CO2 control (min)
W
20
0/600