Information for the specialist - Configuration
CO2
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Freeze protection
Defrosting
Room air controller
Table 4-34 Settings for PID-control - Room air control
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
100
0/1000
I-time (s)
W
300
0/9999
Extract air controller
Table 4-35 Settings for PID-control - Extract air control
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
33
0/1000
I-time (s)
W
100
0/9999
CO2
Table 4-36 Settings for PID-control - CO2
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
100
0/1000
I-time (s)
W
100
0/9999
D-time (s)
W
0
0/9999
Sequence A to D
Table 4-37 Settings for PID-control - Sequence A to D
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
10
0/1000
I-time (s)
W
100
0/9999
D-time (s)
W
0
0/9999
52 (76)