Information for the specialist - Configuration
Freeze protection
Table 4-38 Settings for PID-control - Freeze protection
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
100
0/1000
I-time (s)
W
100
0/9999
D-time (s)
W
0
0/9999
Defrosting
Table 4-39 Settings for PID-control - Defrosting
Variable
Read/Write
Default value
Min/Max
Note
P-band
W
16
0/1000
I-time (s)
W
240
0/9999
D-time (s)
W
0
0/9999
4.4.6
Manual / Auto
Ventilation
Manual/Auto
Ventilation unit
Fan controls
Heater
Exch. /Mix. Damper
Cooler
Add. heater
Change Over
Supply air fan
Extract air fan
Outdoor Air Damper
Exhaust Air Damper
Sum Alarm
Extra TC
Free cooling indic.
Optigo
Ardo