Information for the specialist - Configuration
Sequence settings
These settings are used the define the start of the sequences when the unit starts. There are two different
modes to start the unit:
✓
Normal start up
✓
Warm (Heat) start up
Normal start up:
The sequence control starts at 100% for the heating sequence which is selected at the parameter
At start up
begin temperature control at 100%
. The default setting is
Heating 1
, which means it starts at 100% for heating
sequence 1 which is the exchanger in the default configuration.
Warm start up:
If the outdoor temperature is lower than the settable limit
Warm start up if outdoor temperature < (°C)
the
unit will start in the warm start mode. A second sequence will start at 100% in this mode if the unit
starts. The default setting is
Heating 2
, which means it starts at 100% for the heating sequence 2 which is
the heater in the default configuration
Table 4-3 Sequence settings
Display
Setting alternatives
Note
Begin temperature control at 100 %
✓
Heating X 0%
✓
Heating X
Warm start up if outdoor temperature < (°
C)
Writable
If warm start begin temperature control at
100 % in
✓
Heating %
✓
Heating X
Fan control
Settings for fan control.
Table 4-4 Settings for fan control
Menu
Setting alternatives
Note
Switch point step 1-2
✓
SAF, Writable%
✓
EAF , Writable %
Hysteresis %
Writable
Fan compensation
Settings for fan compensation
Optigo
Ardo
manual, Rev. A
39 (76)