Information for the specialist - Configuration
Supply air controller
Table 4-16 Setpoints for supply air control
Variable
Read/Write
Default
value
Min/Max
Note
Actual supply air temperature (°C)
R
Setpoint adjustment (°C)
W
0
-10/10
Actual setpoint supply air (°C)
R
Setpoint adjustment low speed (°C) W
0
-50/50
Setpoint adjutment high speed (°C) W
0
-50/50
Summer mode: Setpoint supply air
(°C)
W
24
-20/150
Summer mode: Outdoor tempera-
ture (°C)
W
24
-20/150
Min limit supply air
W
12
10/150
Max limit supply air
W
30
10/150
Controller output (%)
R
CO
2
Table 4-17 Setpoints for CO
2
control
Variable
Read/Write
Default
value
Min/Max
Note
Actual CO2 (ppm)
R
Setpoint (ppm)
W
1000
0/2000
Fans
Table 4-18 Setpoints for fans
Variable
Read/Write
Default
value
Min/Max
Note
Setpoint low speed supply air fan
(%)
W
25
0/100
Setpoint normal speed supply air
fan (%)
W
50
0/100
Setpoint high speed supply air fan
(%)
W
75
0/100
Setpoint low speed extract air fan
(%)
W
25
0/100
Setpoint normal speed extract air
fan (%)
W
50
0/100
Setpoint high speed extract air fan
(%)
W
75
0/100