Information for the specialist - Configuration
Table 4-11 Analog outputs
Variable
Settings
Note
Terminal
✓
Off
✓
AO 1…5
The number of terminals are depending on Optigo
Ardo
model
Range output
✓
0…10 V
✓
2…10 V
✓
10…2 V
✓
10…0 V
Digital outputs, DO
Digital outputs can be NC (Normally Closed) or NO (Normally Opened).
See
Appendix C Input and output lists
for a complete list of inputs and outputs.
W
Waarrnniinngg!! Configuration of a physical output to more than 1 function will cause in an undefined behav-
iour of the controller. The alarm- IInntteerrnnaall eerrrro
orr will then become active.
Table 4-12 Digital outputs
Variable
Settings
Note
Terminal
✓
Off
✓
DO 1…7
The number of terminals are depending on Optigo
Ardo
model
NC / NO
✓
NO
✓
NC
✓
NC (Normally closed )
✓
NO (Normally open)
4.3.4
Other configuration
Configuration
Communication
TCP/IP
Save and restore
Communication
The controller uses TCP/IP.
In this menu it's possible to turn on and off DHCP and set a static IP-address.
Save and restore
Save and restore:
✓
Local settings
✓
Factory settings
Optigo
Ardo
manual, Rev. A
43 (76)