Alarm text in Exigo
The alarm text that is displayed in the Exigo on activated alarm is shown in column 2,
Alarm text
.
This text can be changed, but only via Exigo Tool. Double-clicking on the alarm text will open a
dialogue box in which various alarm parameters, including the alarm text itself, can be changed.
The alarm text, including any possible space, may not consist of more than 38 characters. These will
be distributed on 2 rows of 19 characters each. If a word in the text extends past the 19th position, the
whole word will be moved to the second row. To avoid this, a hyphen can be added in the 19th
position, followed by a space and then the rest of the word.
Example:
The message ”Sensor error relative humidity supply air” consists of 40 characters, but
since the third word extends past the 19th position, the following will be shown in the display:
Sensor error
Relative humidity su
9 Sept 08:52 Class B
However, if the text is changed to: “Sensor error RH supply air”, it will instead result in:
Sensor error RH
supply air
9 Sept 08:52 Class B