12
Chapter 5
Menu bar
Exigo tool manual
Search for controllers
If, on startup, Exigo Tool fails to establish contact with a connected controller it is usually due to an
address mismatch. This function will search through all the possible addresses and list the addresses
of the unit that is connected to the computer. These addresses are then written into the address fields
in the folder
Configuration / System
.
Set controller date and time
Synchronizes the controller date and time with the computer date and time.
Change controller address
This function is used for changing the addresses of the connected controller. The address is normally
254:254. If the controller is intended to be used in an EXOline network, the addresses must be changed
since the connected controllers have different addresses.
Reload controller
Downloads the current control program from Exigo Tool to the controller.
Use this function to install updated program revisions. Note, though, that since the hardware differs
between controllers of different sizes, the Exigo Tool program and the Exigo model must be
compatible.
The below dialogue window will be displayed: