Regency
®
PG36 Gas Fireplace
|
19
installation
Diagram 5
7)
Before connecting the horizontal run of flue pipe
to the flue termination, slide the Wall Thimble
(Part # 46DVA-WT) over the flue pipe.
8)
Slide the appliance and flue assembly towards
the wall carefully inserting the flue pipe into the
flue cap assembly. It is important that the flue
pipe extends into the flue cap sufficient distance
so as to result in a minimum pipe overlap of
1-1/4 inches. Secure the connection between
the flue pipe and the flue cap by attaching the
two sheet metal strips extending from the flue
cap assembly into the outer wall of the flue
pipe. Use the two sheet metal screws provided
to connect the strips to the pipe section. See
Diagram 4.
Horizontal Terminations
Install the flue system according to the
manufacturer's instructions included with the
components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the way when the flueing system is attached.
If this is the case, you may want to adjust the
location of the unit. Rough in the gas preferably
on the right side of the unit and the electrical
(junction block is on the left side) on the left.
2) Simpson Dura-vent Co Axial Flue pipe and
fittings are designed with special twist-lock
connections to connect the flueing system to
the appliance flue outlet. A twist-lock appliance
adaptor is an available option that must be used
in conjunction with the Simpson Dura-Vent Co
Axial Flue GS system.
3) Put a bead of high-temp silicone inside the outer
section of the adapter and a bead of Stove Mate
on the inner collar. Slip the adapter over the
existing inner and outer flue collar and fasten to
the outer collar only with the 3 supplied screws
(drilling pilot holes will make this easier). Level
the fireplace and fasten it to the framing using
nails or screws through the nailing strips.
4) Assemble the desired combination of pipe and
elbows to the appliance adaptor and twist-lock
for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and
fittings, are designed to slide straight onto
the male ends of adjacent pipes and fittings,
by orienting the four pipe indentations so
they match and slide in to the four entry slots
on the male ends, Diagram 1. Push the pipe
sections completely together, then twist-
lock one section clockwise approximately
one-quarter turn, until the two sections are
fully locked. The female locking lugs will not
be visible from the outside, on the Black
Pipe or fittings. They may be located by
examining the inside of the female ends.
Diagram 1
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature silicone
sealant to outer pipe on every twist-
lock joint.
b)
Horizontal runs of flue must be supported
every three feet. Wall straps are available
for this purpose.
5)
Mark the wall for a 254mm x 254mm square
hole. The center of the square hole should line
up with the centerline of the horizontal pipe.
Cut and frame the 254mm square hole in the
exterior wall where the flue will be terminated.
If the wall being penetrated is constructed of
non-combustible material, i.e. masonry block or
concrete, a 178mm dia. 191mm dia. (for flex)
hole is acceptable.
Diagram 2
Note:
a)
The horizontal run of flue must be level, or
have a 1/4 inch (6mm) rise for every 1 foot
(.3m) of run towards the termination. Never
allow the flue to run downward. This could
cause high temperatures and may present
the possibility of a fire.
b)
The location of the horizontal flue
termination on an exterior wall must meet all
local and national building codes, and must
not be blocked or obstructed. For External
Flue Terminal Locations, see diagram in
the "Exterior Flue Termination Locations"
section.
6)
The arrow on the flue cap should be pointing
up.
Insure that the 1-1/2" clearances to
combustible materials are maintained. Install
the termination cap, diagram 5.
The four wood screws provided should be
replaced with appropriate fasteners for stucco,
brick, concrete, or other types of sidings.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or furring strips must be used to
ensure that the termination is not
recessed into the siding.
Note: With Dura-Vent,
the minimum
h e i g h t i s
achieved by
installing a 90
o
elbow directly
to the flue
adaptor.
Diagram 4
Diagram 3
9)
Install wall thimble in the center of the 10" square
and attach with wood screws (Diagram 5).