installation
Clearances for Flush Front
NOTE: The minimum floor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel*
Minimum
178 mm
Ceiling
from top of unit.
813 mm
Side Wall Clearance
Flush Front
152 mm
Horizontal Flue Clearances
Top
51 mm
Side
38 mm
Bottom
38 mm
Vertical Flue Clearances
32 mm
Alcove Clearances**:
Max. Depth
914 mm
Min. Width
1219 mm
Min. Height
1829 mm
* see mantel clearance instructions
(Refer to the "Combustible Mantels," & "Mantel Leg
Clearances" sections.)
Clearances
The clearances listed below are Minimum distances
unless otherwise stated:
A major cause of chimney related fires is failure
to maintain required clearances (air space)
to combustible materials. It is of the greatest
importance that this fireplace and flue system
be installed only in accordance with these
instructions.
Diagram 1
Locating Your Fireplace
1. When selecting a location for your fireplace,
ensure that the clearances outlined on this page
are met.
2. Provide adequate clearances for servicing.
3. The appliance must be installed on a flat, solid,
continuous surface (e.g. wood, metal, concrete).
This may be the floor, or raised up on a platform
to enhance its visual impact. If the appliance is
going to be installed on carpeting, combustible
linoleum tile or other combustible material other
than wood flooring, the appliance must be
installed on a metal or wood panel extending
the full width and depth of the appliance.
4. The PG36 Co-Axial Flue Gas Fireplace can be
installed in a recessed position or framed out
into the room as in A, B, C, D. See Diagram 1.
5. The PG36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which meet
the clearances listed on this page.
6. We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before actually
installing this appliance. Have an authorized
inspector, dealer, or installer review your plans
before installation.
Note: For flue terminations see the
"Exterior Flue Termination
Locations" section.
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into Wall/Alcove
D)
Corner
WARNING
Fire hazard is an extreme risk if
these clearances are not adhered
to.
Min.
152mm
775mm
Top of Unit
813 mm to Ceiling
PACKAGING:
The unit and its contents are packaged
to prevent damage during transport.
After unboxing, remove and dispose of
the cardboard spacers, plastic wrap, and
protective film on the glass door.
Before commissioning of the unit, carefully
remove the logs from inside the unit and set
them aside.
Refer to subsequent instructions on proper
setup and safety check before commissioning
the unit.