16
|
Regency
®
PG36 Gas Fireplace
installation
Flueing Arrangements - Vertical Terminations
SIMPSON DURA-VENT CO AXIAL FLUE GS SYSTEM
(Propane & NG)
The PG36 is approved for a 7.0m vertical, with a maximum 3.7m horizontal offset using two 90
o
elbows
(two 45
o
elbows equal one 90
o
elbow) with
Simpson Dura-Vent Co Axial Flue GS
flue systems for
Propane and NG, as per diagram 1.
The PG36 is approved for a 11.3m straight vertical, including a 0.5m horizontal offset using two 90
o
elbow (two 45
o
elbows equal one 90
o
elbow) with
Simpson Dura-Vent Co Axial Flue GS
flue systems
for Propane and NG, as per the diagram 2.
•
Flue must be supported at offsets
• Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Fireplace,"
"Combustible Mantels," "Mantel Leg Clearances" & "Framing and Finishing" sections.
Note: Must use optional flue adapter when using Simpson Dura-Vent pipe
(Part # 510-994).
Note: Regency
®
Co Axial Flue System (Flex) is only approved for horizontal terminations.
Diagram 1
Diagram 2