Greenfire® GF1500L-2 Gas Fireplace
installation
Non Combustible Requirements
Flushed Finishing & Framing with Non Combustible Material
The seven fireplace opening standoffs which are located on this unit can be removed
when non combustible material is installed flush with the unit.
(see P. 13).
Non-combustible finishing material on the top and sides must also be used.
871 mm
605 mm
1432 mm
Non-combustible
Combustible
Combustible
Steel Stud
on edge
Timber Stud
Timber Stud
159 mm
446 mm
Non-Combustible
Material
Combustible
Material
Finished
Material
* diagrams shown below are
with top nailing strip removed.
12mm
25mm
38mm
Unit
Unit
Unit
MINIMUM THICKNESS OF THE FINISH MATERIAL: 12MM
A minimum thickness of 12mm non-
combustible facing is required.
NO
TE
• For flush finishing, the top nailing strip must be removed and a non-combustible
steel stud support added.
NO
TE
• The appliance must be installed on
a flat, solid, continuous surface For
example a wood, metal or concrete
floor. In a raised (on the wall)
application the appliance must be
installed on a metal or wood panel
extending the full width and depth of
the appliance.