Greenfire® GF1500L-2 Gas Fireplace
| 15
installation
Clearances For Non Combustible Flush Finishing with Mantel
Due to the extreme heat this fireplace emits, the mantel
clearances are critical.
Combustible mantel clearances from top of front facing are shown
in the diagram on the right.
Non Combustible Mantel Leg Clearances
Mantel leg & Non-combustible finishing clearances as per diagram: (Flushed Finish)
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
83mm
Non-combustible
83mm
Non-combustible
Combustible Material
(152 mm)
(305mm)
(0 mm)
To Uni
t
Base
(617 mm)
(335 mm)
Top of
Fireplace
Opening
(589mm)
(305 mm)
(457 mm)
(254mm)
Non-Combustible facing (min.12 mm)
Non-Combustible steel stud
846 mm to underside
of steel stud
(100mm)
(310 mm)
(200mm)
(385 mm)
NO
TES
• For a flushed finish using non-combustible finishing, seven
13mm stand-off tabs around the fireplace opening must
be broken off. The top nailing flange cannot be used and a
non-combustible steel stud must be installed to support the
non-combustible facing.
• Ensure the paint that is used on the mantel and the facing
is high quality or the paint may discolour.