Controller
Reflexomat with Basic controller — 20.06.2017 - Rev. C
English — 45
ER Code
Alarm
Floating
contact
Causes
Remedy
Alarm reset
05
Compressor run time
-
•
Set value exceeded.
•
Severe water loss in
the system.
•
Air lines leaking.
•
Solenoid valve in the
overflow line does not
close.
•
Check set value in the
Customer or Service menu.
•
Check the water loss and
correct, if necessary.
•
Seal any leak in the air system.
•
Check functioning of the
"PV1" solenoid valve.
-
06
Make-up time
-
•
Set value exceeded.
•
Water loss in the
system.
•
Make-up line not
connected.
•
Make-up rate
insufficient.
•
Make-up hysteresis
too low.
•
Check set value in the
Customer or Service menu.
•
Check water level.
•
Connect make-up line
"Quit"
07
Make-up cycles
-
Set value exceeded.
•
Check set value in the
Customer or Service menu.
•
Seal any leak in the system.
"Quit"
08
Pressure measurement YES
Controller receives
incorrect signal.
•
Connect the plug.
•
Check functioning of the
pressure sensor.
•
Check the cable for damage.
•
Check the pressure sensor.
"Quit"
09
Level sensor
YES
Controller receives
incorrect signal.
•
Check functioning of the load
cell.
•
Check the cable for damage.
•
Connect the plug.
"Quit"
10
Maximum pressure
-
•
Set value exceeded.
•
Overflow line
disabled.
•
Dirt trap clogged.
•
Check set value in the
Customer or Service menu.
•
Check functioning of the
overflow line.
•
Clean the dirt trap.
"Quit"
11
Make-up quantity
-
"With water meter" must
be activated in the
Customer menu.
•
Set value exceeded.
•
Severe water loss in
the system.
•
Check set value in the
Customer or Service menu.
•
Check water loss in the system
and repair, if necessary.
"Quit"