Installation
20 — English
Reflexomat with Basic controller — 20.06.2017 - Rev. C
6.3.2
Tank installation
ATTENTION
Damage due to improper installation
Additional device stresses may arise due to the connection of pipes or system equipment.
•
Ensure that pipes are connected from the device to the system without stresses being induced.
•
If necessary, provide support structures for the pipes or equipment.
Comply with the following notes regarding the installation of
the primary tank and the secondary tanks:
•
All flange openings at the tanks are viewing and
maintenance openings.
– Place the tanks with sufficient distances to sides and
ceiling.
•
Install the tanks on a level surface.
•
Ensure rectangular and free-standing position of the tanks.
•
Use only tanks of the same type and dimensions when
using secondary tanks.
•
Ensure proper functioning of the "LIS" level sensor.
ATTENTION Property damage caused by overpressure. Do
not attach the tanks firmly to the floor.
•
Install the control unit on the same level as the tanks.