Controller
42 — English
Reflexomat with Basic controller — 20.06.2017 - Rev. C
This value is only displayed if "YES" has been set in the "With softening" menu option.
•
Manufacturer specification for the replacement interval of the softening cartridges,
regardless of the calculated soft water capacity. The system displays the "Softening"
message.
Replacement
18 months
Recommended maintenance messages.
Next maintenance
Off:
Without maintenance recommendation.
012 months
001 – 060:
Maintenance recommendation in months.
For the output of messages to the floating contact, see chapter 9.2.2 "Messages" on
page 44 .
Floating fault contact
YES
yes:
Output of all messages.
no:
Output of all messages identified with
"xxx"
("05", for example).
Switch to the "Fault memory" main menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
Fault memory
˃
The last 20 alarms are stored with fault type, date, time, and fault code.
See the chapter "Messages" for more information about the ER... messages.
ER 01…xx
05
Fault type | Date | Time
Switch to the "Parameter memory" main menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
Parameter memory
˃
The last 10 entries of the minimum working pressure are stored with date and time.
P0 = xx.x bar
Date | Time
The system displays the values for the volume and the diameter of the "RG" primary tank.
•
If you identify differences to the information provided on the primary tank's
nameplate, please contact the Reflex Customer Service.
Tank info
00800 l
Information about the software version
Reflexomat
V1.00