Installation
30 — English
Reflexomat with Basic controller — 20.06.2017 - Rev. C
Terminal
number
Signal
Function
Wiring
1
PE
230 V power supply via mains cable and plug.
Factory
2
N
3
L
4
PE
Compressor for maintaining the pressure.
Factory
5N
N
6 M1
M 1
7
Y2
Overflow solenoid valve.
•
For controlling pressure maintenance in the overflow line.
Factory
8
N
9
PE
10
Y 1
230 V output for make-up.
•
To control a Reflex Fillcontrol, for example.
User, optional
11
N
12
PE
13
COM
Group message (floating).
User, optional
14
NC
15
N.O.
16
Not assigned
External make-up request.
•
Not used with the Reflexomat.
---
17
Make-up (230 V)
18
Make-up (230 V)
19
PE shield
Level analogue input.
•
Display at the controller.
•
Activation of the make-up.
Pre-wired, sensor plug
must be attached on-
site
20
- Level (signal)
21
+ Level (+ 18 V)
22
PE (shield)
Pressure analogue input.
•
Display at the controller.
•
Control of pressure maintenance.
Factory
23
- Pressure (signal)
24
+ Pressure (+ 18 V)
25
0 – 10 V (correcting
variable)
Motor ball valve
•
Not used with the Reflexomat.
---
26
0 – 10 V (feedback)
27
GND
28
+ 24 V (supply)
29
A
RS-485 interface.
User, optional
30
B
31
GND
32
+ 24 V (supply) E1
Supply for E1 and E2.
Factory
33
E1
Contact water meter (in Fillset, for example), see chapter 4.6
"Optional equipment and accessories" on page 14 .
•
Evaluation of the make-up.
– If contact 32/33 is closed = meter pulse.
User, optional
34
E2
Insufficient water switch.
•
Not used with the Reflexomat.
– If contact 32/34 is closed = OK.
---
Содержание Refexomat RSC